System status messages

System status messages

The list of messages you may see in the UI, possible causes and actions you should take to resolve them.

Message

Cause

Action

Lamp failure

A problem with the light source

Check the light source

Short circuit

Short circuit on load - over 100% of nominal load

Remove short circuit or decrease load

Open circuit

Open circuit - 0% of load detected - the light source probably disconnected

Reconnect or replace the light source

Load decrease

Decrease of load detected - the LED source is partially defected

Fix or replace the light source

Load increase

Increase of load Detected - the LED source is partially defected or a new light source is connected

Fix or replace the light source

Current protector active

Active current protection - load anomaly detected

Check the actual load of this driver

Thermal shutdown

Temperature too high - luminaire is turned off

Cool the luminaire and prepare better temperature conditions for this device

Thermal overload with light level reduction

Temperature too high - the power of the luminaire is reduced - if the temperature keeps rising, thermal shutdown may occur

Cool the luminaire and prepare better temperature conditions

Reference measurement failed

Incorrect configuration of the luminaire (manufacturing defect)

Replace the luminaire

Circuit failure

Problem with the emergency module

Replace the emergency module

Battery duration failure

Battery operation is enabled but the battery backup duration time is below the minimum value

Replace the battery

Battery failure

Battery short-circuit, disconnection or battery defected

Replace the battery

Message

Action

Message

Action

Unconfigured network

Unconfigured network detected

You have not grouped the Vertex controllers into a network. Group them using NetConfig.

DALI Devices Discovery Error

Dali Point does not discover new DALI devices

Vertex detects an unaddressed device on the bus, but after an addressing attempt, the device continues to respond as unaddressed.

Replace the luminaire power supply or ensure proper power supply operation.

DALI2 Devices Discovery Error

Dali Point does not discover new DALI2 devices

Communication Error

Communication Error detected

Check for any visible damage to the DALI bus wiring and restart the Vertex controller. If the issue persists, contact your LMS sales representative.

Current Overflow Error

Current is greater than 230mA on port

Reduce the number of devices so that the maximum current does not exceed the allowed limit.

Fuse Error

Fuse Error Detected

Contact your LMS sales representative.

Port 230V Error

Voltage with value of 230V detected on port

Check the installation to locate the 230 V connection point.

DALI Addresses Overload Error

Too many DALI devices detected on port

Reduce the number of devices so that the maximum number of addresses does not exceed the allowed limit.

DALI2 Addresses Overload Error

Too many DALI2 devices detected on port

Short Circuit Error

Short Circuit Error detected

Check the installation to locate the short circuit.

Temperature Too High Error

Detected that temperature is too high on port

Check the ambient temperature and make sure it does not exceed the allowed limit. Reduce the number of devices on this port.

Update Failed Error

Problem with Dali Point updating

Run the update again. If the issue persists, contact your LMS sales representative.

Low Disk Space

Data partition free space is critically low. Free up space to avoid system issues

Perform a factory reset. If the issue persists, contact your LMS sales representative.

Log Write Failure

Failed to save logs to disk. The data partition may be full or read-only

Restart the device. If the issue persists, contact your LMS sales representative.

Vertex Disconnected

Problem with connecting to vertex

No communication. Check the power supply and the LAN connection.

Low Disk Space Warning

Data partition free space is running low. Consider freeing up space

No action is required. However, if the percentage value drops rapidly over time, contact your LMS sales representative.

Non-normative frame timing detected

Detected non-normative DALI frame timing on some of the devices. Consider replacing them with devices following DALI standard

Check the quality of the connected devices.

Backup devices failures

Check for warnings reported by other Vertex controllers.