This documentation is for older software versions (up to 3.1.29). If you have software version 3.1.30 or higher, go to MODERN Home

(Classic) LMS E2D VERTEX APC G3

Functions

  • Lighting control for DALI-2 compatible luminaires

  • Support for DALI-2 input devices (e.g. sensors and panels)

  • A completely autonomous controller

  • 3 DALI ports that support up to 64 devices (up to 192 devices per one Vertex controller)

  • Error detection signaled via LED indicators

  • A built-in online lighting control app

  • The system can be scaled using a standard Ethernet interface

  • Creating an extensive, cross-controller logic

  • ON/OFF control over the DALI ports using buttons on the front panel

Technical parameters

Protection class

II

Ethernet port

10/100 Mbit - RJ45

USB port

2 x USB-A, USB 2.0

Short-circuit DALI bus current

3 x 250 mA

Continuous DALI bus currrent

3 x 230 mA

Power supply protection

630 mA fuse

DALI bus protection
Both vertex 2 and vertex 3 have a built-in DALI current limitation. In the event of a short circuit, the contact current is limited to 160 mA (Vertex 2) and 240 mA (Vertex 3). The maximum voltage on the DALI bus is 19-20 V DC and it is in the safe voltages. In the event of a 230 V AC short-circuit to the DALI Vertex 2 and 3 bus it will show in the user's graphical interface. In addition, in the Vertex 3 fuse will burn, which is only replaceable by the production plant. During a 230 V AC short-circuit to the DALI bus, active devices (sensors and buttons) may be burned. All work on the DALI bus must be carried out with the power supply 230 V for the Vertex unit switched off.

VERTEX ApC status LEDs

LED

Status

Description

LED

Status

Description

Power

ON

Device on

OFF

Device off

Status

GREEN

Device ready to operate

RED

Error with the device (see Troubleshooting)

OFF

Device startup sequence

Cloud

ON

Glamox connect connection established

BLINKING

Not connected to Glamox Connect

DALI

ON

DALI bus short circuit

BLINKING*

DALI bus transmission

BLINKING**

AC power voltage on DALI bus

*For each DALI frame


**1 Hz frequency

How to use it in the LMS design?

See the principles of E2D design and good practices.

How to commission it?

See the Commissioning section.

 

For more information, search the Ethernet2DALI Knowledge Base.