This documentation is for older software versions (up to 3.1.29). If you have software version 3.1.30 or higher, go to MODERN Home

(Classic) Sensor: LMS DALI-2 PIR CLS LA SENSOR-R

Compare withe a similar sensor LMS DALI-2 PIR CLS SENSORHEAD 10M

The DALI-2 compatible multisensor is designed for a wide range of usage from the production area to the offices. Using accessories may increase the IP index to IP54 which allows mounting the sensor even in a less friendly environment. The sensors deliver very good detection coverage and up to 10 m of the mounting height.

How to use it in LMS design

To place the multisensor in the project, you need to remember the typical Ethernet2DALI limitations. Upgrading the sensor to IP54 requires a special mounting box.

Technical data

Operating voltage

DALI

Installation height

2 – 10 m

Minimum height

>1.7 m

Installation type

Ceiling installation

Stand-by consumption

≤10 mA

Size of concealed housing

Ø55 mm (NIS, PMI)

Ambient temperature

-15°C ... 50°C

Type of protection

IP54 (when fitted)

Detection range

Mounting height (A)

Sitting (S)

Diagonally (T)

2 m

16 m² | 4.5 m

380 m² | 22 m

2.5 m

24 m² | 5.5 m

415 m² | 23 m

3 m

28 m² | 6 m

452 m² | 24 m

3.5 m

38 m² | 7 m

452 m² | 24 m

6 m

---

452 m² | 24 m

10 m

---

491 m² | 25 m

How to commission it?

To program logic within the Node-RED tool you need to use a DALI2 Devs Common node, which is available in the node palette on the left-hand side of Node-RED UI. 

Click this node to enter the configuration window. Choose the serial number of the device in the Serial Number field. Uncheck the Motion/presence sensor checkbox. Below you have two fields where you can set the presence and transition time duration.

Then click Done in the upper right corner of the window.

Then you need to find the vertex action node in the palette. Set Mode as Motion sensor. Then select the group you want to control by this multisensor. Next, you should define actions in Presence, Transition, and No presence fields.  Define these actions as you need.

Don't forget to connect all your nodes and be sure that the vertex cluster node is present in your flow! 

Then click Deploy button at the upper-right corner of the Node-RED.

Import the ready flow using the code below:

[ { "id": "e0e1af9.6a3855", "type": "DALI2 Devs Common", "z": "810b6cdc.028bf", "name": "", "outputs": 1, "uid": "D7BFBFCF00891400", "savedSettings": [ { "instanceType": 3, "isDisabled": false, "dali2t1": "", "dali2t2": "" }, { "instanceType": 4, "isDisabled": true }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" }, { "instanceType": 1, "isDisabled": true, "mode": "normal" } ], "x": 400, "y": 180, "wires": [ [ "3ad2631c.8574cc" ] ] }, { "id": "3ad2631c.8574cc", "type": "vertex action", "z": "810b6cdc.028bf", "name": "", "typeButton": "motionsensor", "bPayload": { "PRESENCE": { "action": "noreact", "group": "0327ffd20adbd58c2cf40fa8b12b9304", "param": null, "priority": "255" }, "TRANSITION": { "action": "noreact", "group": "0327ffd20adbd58c2cf40fa8b12b9304", "param": null, "priority": "0" }, "NOPRESENCE": { "action": "noreact", "group": "0327ffd20adbd58c2cf40fa8b12b9304", "param": null, "priority": "254" } }, "bState": "", "defaultpriority": true, "x": 620, "y": 180, "wires": [ [ "ad4e04de.d85e18" ] ] }, { "id": "ad4e04de.d85e18", "type": "vertex cluster", "z": "810b6cdc.028bf", "userouting": false, "rate": 5, "x": 810, "y": 180, "wires": [] } ]

 

 

Related pages