(Classic) LMS E2D VERTEX APC G3
Functions
Lighting control for DALI-2 compatible luminaires
Support for DALI-2 input devices (e.g. sensors and panels)
A completely autonomous controller
3 DALI ports that support up to 64 devices (up to 192 devices per one Vertex controller)
Error detection signaled via LED indicators
A built-in online lighting control app
The system can be scaled using a standard Ethernet interface
Creating an extensive, cross-controller logic
ON/OFF control over the DALI ports using buttons on the front panel
Technical parameters
Protection class | II |
---|---|
Ethernet port | 10/100 Mbit - RJ45 |
USB port | 2 x USB-A, USB 2.0 |
Short-circuit DALI bus current | 3 x 250 mA |
Continuous DALI bus currrent | 3 x 230 mA |
Power supply protection | 630 mA fuse |
DALI bus protection
Both vertex 2 and vertex 3 have a built-in DALI current limitation. In the event of a short circuit, the contact current is limited to 160 mA (Vertex 2) and 240 mA (Vertex 3). The maximum voltage on the DALI bus is 19-20 V DC and it is in the safe voltages. In the event of a 230 V AC short-circuit to the DALI Vertex 2 and 3 bus it will show in the user's graphical interface. In addition, in the Vertex 3 fuse will burn, which is only replaceable by the production plant. During a 230 V AC short-circuit to the DALI bus, active devices (sensors and buttons) may be burned. All work on the DALI bus must be carried out with the power supply 230 V for the Vertex unit switched off.
VERTEX ApC status LEDs
LED | Status | Description |
---|---|---|
Power | ON | Device on |
OFF | Device off | |
Status | GREEN | Device ready to operate |
RED | Error with the device (see Troubleshooting) | |
OFF | Device startup sequence | |
Cloud | ON | Glamox connect connection established |
BLINKING | Not connected to Glamox Connect | |
DALI | ON | DALI bus short circuit |
BLINKING* | DALI bus transmission | |
BLINKING** | AC power voltage on DALI bus |
*For each DALI frame
**1 Hz frequency
How to use it in the LMS design?
See the principles of E2D design and good practices.
How to commission it?
See the Commissioning section.