Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Sometimes, there might be a situation that devices won’t be properly read and addressed by the VERTEX controller. By clearing the devices on the bus(es) you can resolve these issues.

Instructions

  1. Log in as an administrator to the VERTEX GUI.

  2. Go to the Actions sections and then select the Vertex/Port.

  3. Select the ports on which you want to clear devices.

    Image Removed

Selecting the port(s) for clearing devices

4. Select Clear devices action from the panel below. Then confirm your selection in a window.

...

If you are in the process of an initial setup make sure that you've completed the previous step: Vertex software updating.

Note

By clearing the devices on the buses you will ensure that all the devices are properly read and addressed. It’s important you know it’s a hard reset of all devices.

Instructions

  1. Choose Setting section [1]

  2. Go to Vertex cluster [2] and log into the Vertex as an administrator.

  3. Click on the Actions [3]drop down list

  4. Choose the DALI bus you’d like to reset. [4]

...

Info

Clearing devices may take a while, usually about 30 seconds. After this operation, the VERTEX controller will again find and address Vertex controller finds the devices connected to the DALI port again and assigns new addresses to them. This may take several minutes.

↪ The next step: 5. Identifying luminaires