Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 3 Current »

Necessary components

LMS WIRELESS SCENE CONTROLLER: Office & Industrial

LMS WIRELESS SCENE CONTROLLER BATTERY


Installation

LMS Wireless Scene Controller:

3-core 230v mains input is required.

LMS Wireless Scene Controller Battery:

For optimum signal transmission ensure installation with sticker face plate facing out and not fully enclosed in a metal housing.

2 x AAA batteries is required.

The batteries will last for more than 5 years with up to 50 activations per day.


Step-by-Step Instructions

  1. https://glamox.atlassian.net/wiki/spaces/WR/pages/3073769976/Copy+of+Installing+LMS+Wireless+Scene+Controller#1.-Creating-a-Scene-Controller-profile%3A

  2. https://glamox.atlassian.net/wiki/spaces/WR/pages/3073769976/Copy+of+Installing+LMS+Wireless+Scene+Controller#2.-Creating-links-from-the-Scene-Controller-to-other-devices%3A

  3. https://glamox.atlassian.net/wiki/spaces/WR/pages/3073769976/Copy+of+Installing+LMS+Wireless+Scene+Controller#3.-Commissioning-scene-controller-buttons%3A

  4. https://glamox.atlassian.net/wiki/spaces/WR/pages/3073769976/Copy+of+Installing+LMS+Wireless+Scene+Controller#4.-Testing-the-scene-operation-using-the-Glamox-Dongle%3A

  5. https://glamox.atlassian.net/wiki/spaces/WR/pages/3073769976/Copy+of+Installing+LMS+Wireless+Scene+Controller#5.-Synchronise-the-Scene-Settings-with-your-Physical-Scene-Controller-device%3A

1. Creating a Scene Controller profile:

1.1. Click 'Profiles' and 'Component' view [1].

1.2. Create a Profile for a Scene Controller.

1.3. Make sure SceneController type is selected [2].

1.4. Make sure the PowerOn level in ‘Driver’ settings is at least 1W [3].

1.5. Click ‘Save Changes’.

image-20241211-142730.png

1.6. Click 'Luminaires' and 'Locate'.

1.7. Simulate a Device (by clicking in the empty Find Column [4] under the Find then drag the orange (simulated) device onto the drawing in an appropriate location.

image-20241211-143203.png

1.8. Click 'Configure' and change the profile of the device to the Scene Controller profile you have created above [5].

image-20241211-143438.png

2. Creating links from the Scene Controller to other devices:

2.1. Click 'Link'.

2.2. Link the Scene Controller to the Devices to be controlled by:

2.3. drawing lines one at a time from the scene controller to the luminaire controller [6] OR,

2.4. highlight a group of devices to be controlled, then click “Link From X” [7] and enter the FULL serial number of the Scene Controller.

image-20241211-143655.png

3. Commissioning scene controller buttons:

3.1. Select 'Scenes' [8] from the main menu at the top of the screen and select the scene controller on the drawing [9].

image-20241211-145403.png

If this displays a set of buttons only, as below, then close this view by clicking 'Edit' and enter the admin pin (0000 by default).

3.2. By default, the scenes are preset with the following parameters [10]:

Scene 1

Max

100% lamp level

Scene 2

On Levels

Masks the Profile(s) OnLevel

Scene 3

Standby Levels

Masks the Profile(s) Standby Level

Scene 4

Min

1% lamp level

Scene 5

Cancel

100% lamp level with 0 second delay

Scene 6

Off

0% lamp level

image-20241211-145457.png

3.3. To change the default profile names, long click on the scene name [11] and click save. To change the lamp on levels for each linked profile, click on the lamp % box [12] and click save.

image-20241211-145928.png

3.4. If you need to remove linked profiles from a particular scene, select ‘Custom’ from the ‘Profiles’ drop down menu [13] and the profiles list will then be editable [14]

image-20241211-150337.png

3.5. If you want to view the additonal scene buttons (7,8,9,10), change the scene delay or untick ’synchronised profiles' [15], then tap on the 'Scenes' navigation button [16] again to show these advanced features.

image-20241211-150525.png

Total time for a scene message = Scene Delay + PIRTimeOut + Fade time + StandbyTime


4. Testing the scene operation using the Glamox Dongle:

4.1. Ensure than the tablet is connected to the DONGLE and stand within RF range of the luminaires.

4.2. Select a Scene (1-6) and click 'Test' [17].

image-20241211-150745.png

4.3. Repeat for each scene and adjust levels as required.


5. Synchronise the Scene Settings with your Physical Scene Controller device:

5.1. Click ‘Luminaires' and 'Locate’.

5.2. If you know the full serial number of the physical device then Change the Serial number from the Simulated 4 digit serial to the real number by Long Clicking the serial number [18] and entering the full 6+ digit number.

image-20241211-151004.png

5.3. Click the simulated device icon on the drawing and it should change from Orange to Blue.

If you are using an LMS Wireless Scene Controller Battery, then you will need to wake the device up before finding it.

To do this, perform one of two actions, either:

  • Short press button one (release), then long press button one and button two together for 5 seconds (release).

OR

  • Short press button one 6 times within 10 seconds.

5.4. If you are using an LMS Wireless Scene Controller you will be able to find the device when clicking ‘Find’ as this does not require a ‘wake up’ sequence.

5.5. Once the LMS Wireless Scene Controller is found, you can drag and drop the physical device over the simulated device.

5.6. Click ‘Yes’ to replace the device.

image-20241211-151114.png

5.7. Click ‘Scenes'.

5.8. All scenes will be red (unsycned), click ‘Sync’ [19] to sync all scene settings with the physical device. All scenes should turn blue once completed.

image-20241211-151300.png

If you are using an LMS Wireless Scene Controller Battery, you need to put the device into a ‘commissioning mode’.

To do this, perform one of two actions, either:

  • Press button one (release), then press and hold button one and button two together for 5 seconds (release).

OR

  • Press button one 6 times within 10 seconds.

Then, press ‘Sync’.

5.9. Click ‘Luminaires’ and make sure the scene controller and devices Configuration and Links are synced.

If using an LMS Wireless Scene Controller Battery, you will need to wait 45 seconds before being able to use a physical scene button after syncing the scenes.

  • No labels