LMS Wireless Scene Controller
Necessary components
LMS WIRELESS SCENE CONTROLLER: Office & Industrial
LMS WIRELESS SCENE CONTROLLER BATTERY
Installation
LMS Wireless Scene Controller:
3-core 230v mains input is required.
LMS Wireless Scene Controller Battery:
For optimum signal transmission ensure installation with sticker face plate facing out and not fully enclosed in a metal housing.
2 x AAA batteries is required.
The batteries will last for more than 5 years with up to 50 activations per day.
Step-by-Step Instructions
Create a Scene Controller profile, if needed use the instructions 6. Creating profiles
Create a simulated device 3. Creating Simulated Devices for the scene controller. Go to Configure and change the profile to the one you created.
Create links from the Scene Controller to other devices 7. Linking
Go to Scenes. Here you will be able to create settings for each button in your scene controller. The Profile with which the scene controller is communicating will be assigned automaticaly.
You can create settings for brightness, colour temperature and RGB or use the default settings as described below. To change the lamp on levels for each linked profile, click on the lamp % box and click save.
If this displays a set of buttons only, as below, then close this view by clicking 'Edit' and enter the admin pin (0000 by default).
By default, the scenes are preset with the following parameters:
Scene 1 | Max | 100% lamp level |
|---|---|---|
Scene 2 | On Levels | Masks the Profile(s) OnLevel |
Scene 3 | Standby Levels | Masks the Profile(s) Standby Level |
Scene 4 | Min | 1% lamp level |
Scene 5 | Cancel | 100% lamp level with 0 second delay |
Scene 6 | Off | 0% lamp level |
Total time for a scene message = Scene Delay + PIRTimeOut + Fade time + StandbyTime
Test the scene operation using the Glamox Dongle. Ensure than the tablet is connected to the DONGLE and stand within RF range of the luminaires. Select a Scene (1-6) and click Test.
Repeat for each scene and adjust levels as required.
Go to Lumianires tab and to Locate. Synchronise the Scene Settings with your Physical Scene Controller device. If you know the full serial number of the physical device then Change the Serial number from the Simulated 4 digit serial to the real number by Long Clicking the serial number and entering the full 6+ digit number.
Click the simulated device icon on the drawing and it should change from Orange to Blue.
If you are using an LMS Wireless Scene Controller Battery, then you will need to wake the device up before finding it.
To do this, perform one of two actions, either:
Short press button one (release), then long press button one and button two together for 5 seconds (release).
OR
Short press button one 6 times within 10 seconds.
Go to Scenes tab, click on Sync and make sure all scenes turned blue.
If you are using an LMS Wireless Scene Controller Battery, you need to put the device into a ‘commissioning mode’.
To do this, perform one of two actions, either:
Press button one (release), then press and hold button one and button two together for 5 seconds (release).
OR
Press button one 6 times within 10 seconds.
Then, press ‘Sync’.
Enter ‘Luminaires’ and make sure the scene controller and devices Configuration and Links are synced.
If using an LMS Wireless Scene Controller Battery, you will need to wait 45 seconds before being able to use a physical scene button after syncing the scenes.