The access point is the one point connected to Glamox Connect. The access point communicates to the gateway(s) on the local network.
...
Components
Access point - Access point: LMS CONNECT RevPi
...
Local gateways to your systems:
Ethernet2Dali (E2D) - LMS E2D VERTEX
...
...
DALI Complete - LMS CONNECT DALI/TCP GATEWAY
...
24 V power supply(s) - LMS E2D POWER SUPPLY 24V 30W
Ethernet switch ports for all access points
...
- you can use LMS E2D IND SWITCH
Internet connection
...
Info |
---|
The Access point needs to be connected to 24 V power as well as ethernet connection. |
Inc drawio | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Example with multiple DALI gateways connected to Glamox Connect
Note |
---|
Glamox Connect monitors luminaires as long as they are powered. If you use the manual power switch, the luminaires will be flagged as missing (Maintenance issue and alert). To avoid this, do NOT mount monitored equipment on a power line with "manual" power switch. |
Gateways limits
There is no hard limit to the number of gateways to 1 access point , but recommendations are as follows:
Ethernet2Dali - Max max 25 gateways (one cluster) per access point
Wireless Zigbee - Max max 10 gateways per access point
DALI Complete - Max max 8 gateways per access point
Gateways details
Ethernet2Dali - detailed information on the Ethernet2Dali gateway can be found here: Ethernet2Dali
Wireless Zigbee - gateway requires PoE or 230 V power supply adapter, as well as an ethernet connection.
DALI Complete - gateway has two ports for DALI connection, so you will need 1 gateway per two DALI lines in your installation. The DALI gateway is physically connected to the DALI lines, as well as connected to your local IP network. The DALI gateway needs 24 V mains connection.
Info |
---|
The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways. |