Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

The access point is the one point connected to Glamox Connect. The access point communicates to the gateway(s) on the local network.

...

Components

  1. Access point - Access point: LMS CONNECT RevPi

...

  1. Core3+ATLAS

  2. Local gateways to your systems:

    1. Ethernet2Dali (E2D) - LMS E2D VERTEX

...

    1. APC 3 (if you already have it in your installation, you don’t need to add another one) with internet connection

    2. Wireless Zigbee - LMS

...

    1. Zigbee Gateway

    2. DALI Complete - LMS CONNECT DALI/TCP GATEWAY

...

24 V power supply(s) - LMS E2D POWER SUPPLY 24V 30W

  1. Ethernet switch ports for all access points

...

  1. - you can use LMS E2D IND SWITCH

  2. Internet connection

...

Info

The Access point needs to be connected to 24 V power as well as ethernet connection.

Inc drawio
baseUrlhttps://glamox.atlassian.net/wiki
diagramNameGlamox Connect equipment.drawio
imgPageId228556814
serviceAttFile
aspectbfe91b75-5d2c-26a0-9c1d-138518896778 1
width950
includedDiagram1
aspectHashe7c056cbb52bb2fcc8de44e0ece2fdd06a689235
pageId228556814
diagramDisplayNameGlamox Connect equipment.drawio
height440

Example with multiple DALI gateways connected to Glamox Connect

Note

Glamox Connect monitors luminaires as long as they are powered. If you use the manual power switch, the luminaires will be flagged as missing (Maintenance issue and alert). To avoid this, do NOT mount monitored equipment on a power line with "manual" power switch.

Gateways limits

There is no hard limit to the number of gateways to 1 access point , but recommendations are as follows:

  • Ethernet2Dali - Max max 25 gateways (one cluster) per access point

  • Wireless Zigbee - Max max 10 gateways per access point

  • DALI Complete - Max max 8 gateways per access point

Gateways details

  • Ethernet2Dali - detailed information on the Ethernet2Dali gateway can be found here: https://glamox.atlassian.net/wiki/spaces/E2D

  • Wireless Zigbee - gateway requires PoE or 230V power supply adapter, as well as an ethernet connection.

  • DALI Complete - gateway has two ports for DALI connection, so you will need 1 gateway per two DALI lines in your installation. The DALI gateway is physically connected to the DALI lines, as well as connected to your local IP network. The DALI gateway needs 24 V mains connection.

Info

The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways.