The access point is the one point connected to Glamox Connect. The access point communicates to the gateway(s) on the local network.What do you need?
...
Components
Access point - Access point: LMS CONNECT RevPi
...
Local gateways to your systems:
Ethernet2Dali (E2D) - LMS E2D VERTEX
...
...
DALI Complete - LMS CONNECT DALI/TCP GATEWAY
...
Ethernet switch ports for all access points
...
- you can use LMS E2D IND SWITCH
Internet connection
...
Info |
---|
The Access point needs to be connected to 24 V power as well as ethernet connection. |
Inc drawio | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Example with multiple DALI gateways connected to Glamox Connect
Note |
---|
Glamox Connect monitors luminaires as long as they are powered. If you use the manual power switch, the luminaires will be flagged as missing (Maintenance issue and alert). To avoid this, do NOT mount monitored equipment on a power line with "manual" power switch. |
Gateways limits
There is no hard limit to the number of gateways to 1 access point , but recommendations are as follows:
Ethernet2Dali : Max - max 25 gateways (one cluster) per access point
Wireless Zigbee : Max - max 10 gateways per access point
DALI Complete : Max - max 8 gateways per access point
Gateways details
Ethernet2Dali
Detailed information on the Ethernet2Dali gateway can be found here: https://glamox.atlassian.net/wiki/spaces/E2D
Wireless Zigbee
The Wireless Zigbee gateway requires PoE or 230V power supply adapter, as well as an ethernet connection.
DALI Complete
...
Info |
---|
The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways. |
...
📋 Related articles
...