Some DALI-2 equipment like buttons may be used as a stand-alone system for controlling the light. In such a situation, these buttons are working in application controller mode. In the E2D, you need to be sure that application controller mode is disabled on these devices. In another case, you may notice the faulty operation of the system. Find how to disable application controller mode in VERTEX GUI.
Instructions
Log in to the VERTEX GUI using the service username and password.
Go to the [1] Device list.
Go to the Groups section and select Settings.
...
3. Select the device which is generating the issues. If you’re not sure which button is the source of problems, check all DALI-2 devices in the cluster.
...
4. Select the option Change Properties at the bottom of the page.
...
5. Select the Basic DALI-2 from the drop-down list.
...
[2] Control devices section.
Mark DALI-2 devices you want to select [3].
Click [4] Actions button.
Click [5] Change device properities.
Send checkbox for the [6] Application controller and set checkbox to [7] Disabled. Then click the [8] Save configuration to device button.
...
The application controller mode is now disabled.