Creating Profiles
Once all luminaires are identified and placed onto the relevant drawing, the next stage is to create profiles in accordance with the Controls Philosophy.
Profiles hold all the parameters to be applied to the device.
To access this menu:
Profiles > Components
Create a new profile by clicking on the drop down box on '100 - Default'
Tap NEW PROFILE TYPE (this will create a copy of the profile selected)
Rename the device as appropriate and Save
Driver
Select the Driver, this will bring up the following options.
Select the Driver for the fitting:
Fixed Output - will not be dimmable will switch on/off only
DALI or 1-10v - will allow the following settings to be applied
Select the required settings for this profile:
OnLevel - the maximum on level of the luminaire
FadeTime - the length of time the fitting will take to fade to Standby Level
StandbyLevel - the level of the luminaire once it is dimmed
StandbyTime - the length of time the luminaire remains at the Standby Level
Set at 127.5 for Never Off
PowerOn - enter the wattage of the luminaire at full output
DayNightEnabled - See Application Note - Building Occupied & Unoccupied Mode
Save Changes
Device type
Select which device you have in the luminaire
G2 Controller - select this if you have a luminaire controller installed
If you have an integral presence sensor (3.3v PIR or Microwave) installed tick PIRENABLED in the PIR Box
PIR Timeout
Click PIR > PIRTIMEOUT to enter the desired timeout.
Microwave - select this if you have a Wireless Radio CMW Sensor
The controller box will automatically change to Microwave
Scene Controller - select this if you are setting up a scene controller
No other settings will be applied and you can Save Changes
E3Module - select this if you have Wireless Radio stand-alone emergency luminaire or integral emergency.
Save Changes
E3Module
If there are emergency fittings of this luminaire type this select the E3 Module Box and the appropriate Emergency Manufacturer. It is not necessary to have a standalone profile for emergency and non-emergency luminaires of the same type.
If there is more than one type of emergency module manufacturer, you will need multiple profiles
Save Changes
LDR
The LDR box can be used to set up Daylight Sensors.
Daylight Sensors - if you have a Recessed IP20 or Surface IP56, review the Spec Guide to determine whether to use Sensor Up or Sensor Down
Device Icon
Once you have set up each profile, you can change the icon so it's easier to identify on the drawing
Tap on the luminaire image in the top left > select from drop down list > save
Repeat the process for as many profiles as you require, remembering to save each profile
Applying Profiles
Once you have created your profiles, they can be applied to Wireless Radio devices.
Select Luminaires > Configure
Select an individual device or group of devices by swiping your finger across a group of devices
Tap Profile and the drop down list will appear
Select the desired profile and it will be applied to the selected luminaires
Repeat the process for all devices
Ensure all the fittings are blue and Synced - using the Sync button in the top left or tapping the individual device
If you make changes to profiles or which profile a device has then you must check that all changes have been synced.
Add Comment