The DALI-2 compatible multisensor is designed for corridors and communication paths because of the elliptical detection area. Using accessories may increase the IP index to IP54 which allows mounting the sensor even in a less friendly environment. The sensors deliver very good detection coverage and up to 6 m of the mounting height.
LMS DALI-2 PIR CLS LA SENSOR-R
LMS DALI-2 PIR CLS LA SENSOR-R Dimensions
How to use it in LMS design
To place the multisensor in the project, you need to remember the typical Ethernet2DALI limitations. The average DALI bus load is 9 mA. The sensor offers both presence and motion detection. Upgrading the sensor to IP54 requires a special mounting box. The sensor will be perfect for corridors and communication paths because of the elliptical presence/motion detection area. During LMS design remember about specifying the detecting directions of the sensor.
Technical data
Installation height | 2 – 6 m |
Minimum height | >1.7 m |
Installation type | Ceiling installation |
Avarage DALI current consumption | 10 mA |
Size of concealed housing | Ø55 mm |
Ambient temperature | -15°C ... 50°C |
Type of protection | IP54 (when fitted) |
Detection range
Mounting height (A) | Diagonally (t) | Head on to (R) |
2 m | 56 m² | 16 m x 3.5 m | 56 m² | 16 m x 3.5 m |
2.5 m | 88 m² | 22 m x 4 m | 72 m² | 18 m x 4 m |
3 m | 135 m² | 30 m x 4.5 m | 90 m² | 20 m x 4.5 m |
3.5 m | 150 m² | 30 m x 5 m | 100 m² | 20 m x 5 m |
4 m | 150 m² | 30 m x 5 m | 100 m² | 20 m x 5 m |
4.5 m | 150 m² | 30 m x 5 m | 100 m² | 20 m x 5 m |
5 m | 150 m² | 30 m x 5 m | 100 m² | 20 m x 5 m |
5.5 m | 150 m² | 30 m x 5 m | 100 m² | 20 m x 5 m |
6 m | 150 m² | 30 m x 5 m | 100 m² | 20 m x 5 m |
The sensor offers 2 instances for motion/presence detection. It means that using one sensor allows for controlling 2 zones independently.
How to commission it?
Go to Sensor Commissioning
0 Comments