This DALI-2 compatible
...
sensor has an rectangular detection area. It is suitable for corridors and
...
aisles. The sensors has very good detection coverage and a mounting height up to 6 m
...
.
...
...
LMS DALI-2 PIR CLS LA SENSOR-R Dimensions
How to use it in LMS design
...
Technical data
...
Installation height
...
2 – 6 m
...
Minimum height
...
>1.7 m
...
Installation type
...
Ceiling installation
...
Avarage DALI current consumption
...
10 mA
...
Size of concealed housing
...
Ø55 mm
...
Ambient temperature
...
-15°C ... 50°C
...
Type of protection
...
IP54 (when fitted)
Detection range
...
Mounting height (A)
...
Diagonally (t)
...
Head on to (R)
...
2 m
...
56 m² | 16 m x 3.5 m
...
56 m² | 16 m x 3.5 m
...
2.5 m
...
88 m² | 22 m x 4 m
...
72 m² | 18 m x 4 m
...
3 m
...
135 m² | 30 m x 4.5 m
...
90 m² | 20 m x 4.5 m
...
3.5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
4 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
4.5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
5.5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
6 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
B29102002
By using mounting boxes you can increase the IP class to IP54 which allows mounting the sensor in challenging environments.
B29011002
IP54
B29011004
IP54
The sensor offers you up to a 30x5m detection area (for the max height of 6m).
Info |
---|
The sensor offers 2 instances for motion/presence detection. It means that using one sensor allows for controlling 2 zones independently. |
How to use it in LMS design
When using the multisensor in a project, you need to remember the typical Ethernet2DALI limitations.
How to commission it?
Go to Sensor Commissioning
Info |
---|
For other sensors look here: E2D components |