The commissioning software allows you to set different settings, within the same profile, to account for periods of time when buildings are operational and when they are unoccupied, except for security staff.

...

Info

All luminaire controllers can perform this operation.

...

Commissioning

...

How to Implement

...

Occupied/Unoccupied mode

...

  1. Go to the

...

  1. Profiles and ensure you are in Component View.

  2. Click on the

...

  1. Driver [1] box.

  2. Ensure that the Basic/Advanced button shows Advanced

...

  1. [2].

  2. Tick DayNightEnabled [3].

  3. Now you can enter a second set of

...

  1. OnLevel,

...

  1. StandbyLevel and

...

  1. StandbyTime settings.

...

...

Info

The

...

PIRTimeout can also be modified in the same way by clicking on the PIR box and following the instructions above [4].

...

Guidance Notes

When Occupied

  • If there are no retriggers within a period of DayNightTimeOut multiplied by 3 then we switch to UnOccupied Mode.

...

  • We wait for the DayNightTimeOut seconds.

  • If there were any retriggers in the period, we

    increment a Counter.

  • If there were no retriggers, we then we decrement the

    Counter.

  • If the Counter gets to 3 then we reset it and switch to

    Occupied Mode.

...

Effects on Energy Savings

The effect on energy saving can be significant and can be viewed via the portal which splits energy use down between occupied and unoccupied mode.

...