This article shows how to connect

...

a Kinetic switch when you have

...

a Dongle connected and luminaire

...

are identified.

Necessary components

...

Info

Requires a Glamox Wireless Radio luminaire with CPW2-SEN sensor with firmware version 6.8.135 or newer, if you have older software go to

...

article

...

Updating LMS WIRELESS DONGLE

...

Step by step instructions

These steps need to be followed in the chronological order, or the commissioning will fail.

  1. https://glamox.atlassian.net/wiki/spaces/WR/pages/edit-v2/2932572163#1.-Enabling-the-Kinetic-Master-Luminaire%3A

  2. https://glamox.atlassian.net/wiki/spaces/WR/pages/edit-v2/2932572163#2.-Establishing-Links-for-Scene-Control

  3. https://glamox.atlassian.net/wiki/spaces/WR/pages/edit-v2/2932572163#3.-Creating-and-Assigning-the-Kinetic-Switch-Scene-Profile%2FSettings%3A

1. Enabling the

...

Kinetic Master Luminaire:

Info

Make sure the desired luminaire is on firmware version 6.8.135 or newer.

1.1. Enter the Luminaires tab [1] and choose

...

to open the configure option. Click on the desired luminaire with CPW2-sen or other WR-G4 device [2] to pair with the

...

Kinetic switch (this will act as the

...

Kinetic Master).

1.2. Click ‘Configuration' [3] and tick the ‘Enable EnOcean’ box (EO) [4]. A virtual

...

Kinetic switch device will appear next to the device on the drawing [5]. The

...

Kinetic Switch ID will be the digits of the luminiare and a zero (on the drawing you will see a shortcut).

...

2. Pairing EnOcean Switch to EnOcean Master luminiare

2.1. Click on the virtual EnOcean Luminaire [6].

2.2. Click the ‘Pair’ button [7] to activate commissioning mode.

...

2.3. Perform the following steps on the physical EnOcean switch:

  • press button for seven seconds

  • Release button

  • Tap the same button

  • Release button

  • Press button for seven seconds

...

Info

Confirmation blink:

Observe the light connected to the EnOcean device. It should blink three times, indicating a successful commissioning.

...

Info

If you have a problem with stuck Kinetic Switch go to Kinetic switch troubleshooting article.

2. Establishing Links for Scene Control

To perform these actions go to the Luminaires tab and to the Link option [

...

6].

...

2.1. Linking virtual

...

Kinetic Switch device and

...

Kinetic Switch Master luminaire to self

Click on the

...

Kinetic Switch Master luminaire [

...

7] and select ‘Link to Self' [

...

8].

Repeat the process for the virtual EnOcean switch device [11] .

...

2.2. Linking virtual

...

Kinetic switch device to

...

Kinetic Master luminaire

Draw a directional presence link from the virtual

...

Kinetic switch [

...

9] to the

...

Kinetic switch Master luminaire [

...

10] .

...

...

2.3. Linking to other Wireless Radio devices

Draw directional prescence links from the virtual

...

Kinetic switch device [

...

11] to other surrounding devices which need to be controlled by the

...

Kinetic switch.

You can also create presence links by highlighting the devices you want to be linked and click ‘Link from x', using the virtual

...

Kinetic switch device serial ID.

...

...

3. Creating and Assigning the

...

Kinetic Switch Scene Profile/Settings:

We now need to create dedicated profiles for the

...

Kinetic switch to work from.

Info

If you will want for one button to set some lights to light level A and some other to light level B etc. you will need to create multiple profiles.

...

3.1. Enter the ‘Profiles’ tab [

...

12] and from the drop down menu [

...

13] , choose ‘NEW PROFILE’.

...

3.2. Make sure the Controller type is set to SceneController [

...

14] and in the Advanced mode [

...

15] the Dim Up/Down option is ticked [

...

16].

Info

Dimming down - Long press on a button

Dimming up - Long press, release and long press again immediately after releasing

...

3.3. Save the changes [

...

17] and remember the profiles number, you will be needing it later.

...

...

3.4. In the ‘Luminaires’ tab, select the new Virtual

...

Kinetic Switch device [

...

18]. Go to ‘Configure’ [

...

19] and from the ‘Scene Profile’ dropdown menu [

...

20] select the newly created

...

Kinetic switch scene profile.

...

...

3.5. Enter the

...

‘Scenes’ tab [

...

21] and select the

...

‘Kinetic Switch Master’ serial number in the Scene Controller drop down menu [

...

22].

...

3.6 Apply the linked profiles from the drop down menu [

...

23] and press 'Sync'.

...

...

3.8 Go back to the ‘Luminaires’ tab and make sure the

...

Kinetic Switch Master Configuration is sync’d.

...

3.9 Proceed to use the

...

LMS Wireless Kinetic switch.

Info

If you are using a 2-button

...

LMS Wireless Kinetic Switch, use scene buttons 3 & 4 in the Commissioning App. If you are using a 4-button

...

LMS Wireless Kinetic Switch, use scene buttons 1,2,3 & 4.

Info

The

...

Kinetic Switch Master serial number is the same as the physical device, plus an additional '0' on the end. Example: Physical device marked as EnOcean Master = 123456, virtual

...

Kinetic Switch Master acting as the scene controller = 1234560

OLD STEP BY STEP

Step by step instructions

To have connection with greenpower switch you have to press button in specific way.

...

  1. Enter the Luminaires tab and choose the open the configure option. Choose master luminaire and turn on enocean checkbox. In the box there will be a change from “-” to “EO”.
    The EnOcean ID will be last three digits of the luminiare and adding a zero.

...

  1. Open the greenpower icon and select the scene profile related to our luminaire.

Go to the Profiles tab and create a profile that you will be using for Greenpower switches and make sure that LiteIP is set to SceneController and Driver is set to DALI. If you would like to dim up and down luminaire also remember to check Dim Up/Down box. Click save changes.

...

Now in the Luminaires tab you can select scene profile for your lumianire.

...

  1. Setting up the scenes

In the luminaires tab click on the EnOcean icon again so that the upper left corner ID number of controller can bee seen.

...

Go To the Scenes tab and select scene controller with the same ID so in this case 10162240. Each scene corresponds to a button . In one scene you can control many luminaire with different profiles.

...

image-20240701-085845.pngImage Removed

image-20240701-085900.pngImage Removed

You can also go into advanced scenes settings. To do that go to the profiles tab and select Advanced

...

If you come back to the scenes tab again there will be much more settings here.

New options that will appear are:
- Rank
- Cmd
- Hops
- Delay
Synchronise Profiles box

...

  1. Linking the luminaires

In the Luminaires tab go to Link and select all luminaires. Then go to the Link From X option, a box will open called “link form” type entire number of greenpower button which you want the luminaires linked to.

...

  1. Pair greenpower switch

As the last step press the Pair button. If pairing is successful the master luminaire should blink three times.

...

4. Pairing Kinetic Switch to Kinetic Master luminiare

4.1. Click on the virtual Kinetic Switch Luminaire [24].

4.2. Click the ‘Pair’ button [25] to activate commissioning mode.

4.3. Perform the following steps on the physical Kinetic switch:

...

  • Press button for ten seconds

  • Release button

  • Tap the same button

  • Release button

  • Press button for ten seconds

...

Info

Confirmation blink:

Observe the light connected to the LMS Wireless Kinetic Switch device. It should blink three times, indicating a successful commissioning.

Info

Once the light is paired, wait an additional 10 seconds before pressing a scene switch button. Failure to do so will interrupt the final pairing process and you will have to repeat step 2.

If you have problems with dimming go to the Kinetic switch troubleshooting article.