Both the DALI and LAN installation should be done according to the design. The installation must be done in accordance with the best practices for electrical work. The type and protection class of the connected devices must be conform with regulations.

DALI installation

...

Note

The DALI installation should be done in compiance with IEC 62386 standard. For more information go to DiiA website

DALI bus cable parameters

Use copper conductors with Wiring for DALI needs a minimum cross-section of 1.5 mm2. Connect the communication buses to the electrical switchgear, in which the VERTEX controllers will be installed, as well as to all actuators (luminaires, buttons and sensors)all devices (input devices and luminaires to the DALI buses of the VERTEX controllers.

DALI bus length

The maximum length of the DALI wiring with a 1.5 mm2 cross-section is 300 m. If that distance is
exceeded or if wiring with an incorrect cross-section is used, the system may not work correctly.

See how to double this distance.

The maximum communication bus length depending on the wire cross-section, according to the DALI standard:

...

Length

...

Minimum wire cross-section

...

up to 100 m

...

.

...

...

0.75 mm2

...

150-300 m

...

1.5 mm2

Electrical conditions for the DALI bus

The correct voltage range for the DALI bus:

  • 9.5 VDC-22.5 VDC5V DC, typicaltypicaly: 16 VDC

Continuous DALI bus current on the DALI bus:

  • 230 mA* for VERTEX ApC

...

  • 16V DC

The continuous current for each DALI bus must not exceed:

  • 230mA for Vertex3

  • 180mA for Vertex2

Info

Device limits on the DALI bus

Remember about the three basic limitations that are important for the correct operation of the Ethernet2DALI system:

  1. Maximum current value limit

  2. Address number limit

  3. Number of sensors and panels on one bus

DALI bus topologies

Use only the permitted DALI bus topologies.Allowable ways to connect DALI devices can be seen here

LAN network installation

The structural network must be installed in accordance with the best practices for electrical work. Use F-UTP category 5e cables. Install the RJ-45 on the cable end and prepare for the connection of network devicesends. The maximum cable distance between the network devices is 100 m.

Note

After completing the The structural cabling, measurements must be performed to verify conformity with ISO 1181 or EN 50173.