This article shows how to connect Kenetic switch when you have BLE Dongle connected and luminaire is identified.
...
1.1. Enter the Luminaires tab [1] and choose the open the configure option. Click on the desired luminaire with CPW2-sen [2] to pair with the EnOcean switch (this will act as the EnOcean Master).
1.2. Click ‘Configuration' [3] and tick the ‘Enable EnOcean’ box (EO) [4]. A virtual EnOcean device will appear next to the device on the drawing [5]. The EnOcean ID will be the digits of the luminiare and a zero (on the drawing you will see a shortcut).
...
2.1. Click on the virtual EnOcean Luminaire [6].
2.2. Click the ‘Pair’ button [7] to activate commissioning mode.
...
To perform these actions go to the Luminaires tab and to the Link option [8].
3.1. Linking virtual EnOcean switch device and EnOcean Master luminaire to self
Click on the EnOcean Master luminaire [9] and select ‘Link to Self' [10].
Repeat the process for the virtual EnOcean switch device [11] .
...
3.2. Linking virtual EnOcean switch device to EnOcean Master luminaire
Draw a directional presence link from the virtual EnOcean switch [12] to the EnOcean Master luminaire [13] .
...
3.3. Linking to other Wireless Radio devices
Draw directional prescence links from the virtual EnOcean device [14] to other surrounding devices which need to be controlled by the EnOcean switch.
...
4.1. Enter the ‘Profiles’ tab [15] and from the drop down menu[16] , choose ‘NEW PROFILE’.
4.2. Make sure the Controller type is set to SceneController [17] and in the Advanced mode [18] the Dim Up/Down option is ticked [19].
Info |
---|
Dimming down - Long press on a button Dimming up - Long press, release and long press again immediately after releasing |
4.3. Save the changes [20] and remember the profiles number, you will be needing it later.
...
4.4. In the ‘Luminaires’ tab, select the new Virtual EnOcean device [21]. Go to ‘Configure’ [22] and from the ‘Scene Profile’ dropdown menu [23] select the newly created EnOcean Scene profile.
...
4.5. Enter the ‘Scene’ tab [24] and select the ‘EnOcean Master’ serial number in the Scene Controller drop down menu [25].
4.6 Apply the linked profiles from the drop down menu [26] and press 'Sync'.
...
4.8 Go back to the ‘Luminaires’ tab and make sure the EnOcean Master Configuration is sync’d.
...