Necessary components

LMS WIRELESS ACCESS POINT: Industrial & Office

...

Factors to consider when installing an Access Point

When installing an ACCESS POINT make sure that it is located in range of at least 20 lumianires in a 75m radius, preferbaly in the center of the luminaires and not in enclosed areas. It can connect to up to a 1000 lumianires using ”hops”. Reliability of signal is though reduced with the number of hops.

...

ACCESS POINTs need a power supply and a connection to the internet. Glamox supply versions for 4G, Ethernet or Wi-Fi connection.

...

Connections

ACCESS POINTs can be supplied with 4G connections or Ethernet and Wi-Fi adapters.

4G

  • An add-on package is available with 12 months data. At the end of the 12 month period, clients can maintain their own SIM contracts.

  • It provides connectivity without involving the client’s IT infrastructure and is generally suitable for all environments which receive a mobile signal.

  • Monitoring uses approximately 1 Gb per 1,000 luminaires per month.

Ethernet

  • Provides a free wired communication.

  • Ethernet is free from interference of Wi-Fi networks, walls or other physical barriers.

  • When using this option it is important to consider the feasibility of installing Ethernet points across an existing building to ensure full coverage.

Wi-Fi

  • Wi-Fi provides a connection where it is difficult to install Ethernet points.

  • When using this option is important to consider the stability of the Wi-Fi connection in the building. If the Wi-Fi fails or the password changes, then the ACCESS POINT will lose connection to the internet and, without providing an alternative connection, cannot be re-established.

...

Security - Ethernet & Wi-Fi Only

The internet connection requires DHCP and the following permissions:

Destination Address

Destination Port(s)

http://sync.liteip.com

TCP 80

TCP 443

http://ws.liteip.com

TCP 80

TCP 443

http://teamviewer.com

TCP 5938

ubuntu01.liteip.com

TCP 443

TCP 1883

mqtt01.liteip.com

TCP 443

TCP 8883

...

Power Consumption

  • 3 W minimum

  • 5 W average

  • 15 W peak

LED Status Codes

Green Status:

Off

Program Not Started

Solid

Connected to Server: Located

4s On 1s Off

Connected to Server: Not Located

1s On 4s Off

Not connected to Server

...