Necessary components

LMS WIRELESS DONGLE

...

Installation

When installing an ACCESS POINT it’s important to consider the following:

...

Info

If you require additional coverage more ACCESS POINTs can be added at anytime and no additional commissioning will be required. Lights can report to more than one ACCESS POINT.

...

Connections

ACCESS POINTs can be supplied with 4G connections or Ethernet and Wi-Fi adapters.

4G

  • A 4G add on pack is available supplied with 12 months data. At the end of the 12 month period, clients can maintain their own SIM contracts.

  • 4G provides connectivity without involving the client’s IT infrastructure and is generally suitable for all environments which receive a mobile signal.

  • Monitoring uses approximately 1 Gb per 1,000 luminaires per month for monitoring with additional data used for.

Ethernet

  • Provides a free wired communication.

  • Ethernet is free from the interference of Wi-Fi networks, walls or other physical barriers.

  • When using this option it is important to consider the feasibility of installing Ethernet points across an existing building to ensure full coverage.

Wi-Fi

  • Wi-Fi provides a connection where it is difficult to install Ethernet points. When using this option is important to consider the stability of the Wi-Fi connection in the building. If the Wi-Fi drops out or the password is changed, then the ACCESS POINT will lose connection to the internet and, without providing an alternative connection, cannot be re-established.

...

Security - Ethernet & Wi-Fi Only

The internet connection requires DHCP and the following permissions:

Destination Address

Destination Port(s)

http://sync.liteip.com

TCP 80

TCP 443

http://ws.liteip.com

TCP 80

TCP 443

http://teamviewer.com

TCP 5938

ubuntu01.liteip.com

TCP 443

TCP 1883

mqtt01.liteip.com

TCP 443

TCP 8883

...

Power Consumption

  • 3 W minimum

  • 5 W average

  • 15 W peak

LED Status Codes

Green Status:

Off

Program Not Started

Solid

Connected to Server: Located

4s On 1s Off

Connected to Server: Not Located

1s On 4s Off

Not connected to Server

Red Status:

Solid

Program Starting

Off

No Faults

1s On 4s Off

< 5% EM Lights Reporting Errors

4s On 1s Off

≥ 5% EM Lights Reporting Errors