Both the DALI and LAN installation should be done according to the design. The installation must be done in accordance with the best practices for electrical work. The type and protection class of the connected devices must be conformed conform with regulations.

  1. DALI installation

  2. LAN network installation

...

Use copper conductors with a minimum cross-section of 1.5 mm2. Connect the communication buses to the electrical switchgear, in which the VERTEX controllers will be installed, as well as to all actuators (luminaires, buttons and sensors).

...

Length

Minimum wire cross-section

up to 100 m

0.5 mm2

100-150 m

0.75 mm2

150-300 m

1.5 mm2

Electrical conditions for the DALI bus

The correct voltage range for the DALI bus:

...

Remember about the three basic limitations that are important for the correct operation of the Ethernet2DALI system:

  1. Maximum current value limit

  2. Number of addresses Address number limit

  3. Number of sensors and panels on one bus

...