Both the DALI and LAN installation should be done according to the design. The installation must be done in accordance with the best practices for electrical work. The type and protection class of the connected devices must be conformed conform with regulations.
...
Use copper conductors with a minimum cross-section of 1.5 mm2. Connect the communication buses to the electrical switchgear, in which the VERTEX controllers will be installed, as well as to all actuators (luminaires, buttons and sensors).
...
Length | Minimum wire cross-section |
---|---|
up to 100 m | 0.5 mm2 |
100-150 m | 0.75 mm2 |
150-300 m | 1.5 mm2 |
Electrical conditions for the DALI bus
The correct voltage range for the DALI bus:
...
Remember about the three basic limitations that are important for the correct operation of the Ethernet2DALI system:
Number of addresses Address number limit
...