Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  1. Access point

  2. Gateway(s)

  3. 24V power supply(s)

  4. Ethernet switch ports for all access points and gateways

Inc drawio
imgPageId
baseUrlhttps://glamox.atlassian.net/wiki
228556814diagramNameGlamox Connect equipment.drawio
imgPageId228556814
serviceAttFile
aspectbfe91b75-5d2c-26a0-9c1d-138518896778 1
width950
includedDiagram1width950
aspectHashe7c056cbb52bb2fcc8de44e0ece2fdd06a689235
pageId228556814
diagramDisplayNameGlamox Connect equipment.drawio
height440

...

The Access point needs to be connected to 24V power as well as ethernet connection. There is no hard limit to number of gateways to 1 access point, but recommendations are as follows

DALI Complete: Max 8 gateways per access point

Wireless Zigbee: Max 10 gateways pr access point

Ethernet2DALI: TBC - One cluster is verified ok

The DALI complete gateway has two port for DALI connection, so you will need 1 gateway per two DALI lines in your installation. The DALI gateway is physically connected to the DALI lines, as well as connected to your local IP network. The DALI gateway needs 24V mains connection.

The Wireless Zigbee gateway can connect up to 100 devices and requires PoE or 230V power supply adapter, as well an ethernet connection.

Detailed information on the Ethernet2DALI gateway can be found here: https://glamox.atlassian.net/wiki/spaces/E2D/overview

The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways.

...