Circadian rythm CCT

Circadian rythm CCT

Circadian rhythm lighting mimics natural daylight patterns to regulate the body's internal clock, promoting alertness during the day with bright, cool light and relaxation in the evening with warm, dim light. This helps maintain healthy sleep-wake cycles, mood, and overall well-being.

To enable this function at one point you will need to contact oour support team. This means that if you know that you will be commissioning a site it is recomended that you contact the support team and set a date.

Before reading this article we recomend visiting Wireless Radio Dashboard Account

Preparing Luminaires

Before you begin, visit this page for important information.

  1. Create a profile – Follow the steps in Creating profiles. Make sure to:

Click on the Driver box and go to Advanced settings. There tick the DT8 both the Enabled and Available checkboxes.

image-20241115-102613.png
  1. Commission sensors and components – Follow the process outlined in Commissioning Wireless Radio Components.

Creating a Virtual Scene Controller

  1. Create a separate virtual scene controller – Use an appropriate profile name, such as CCT Scene. Follow the steps in LMS Wireless Scene Controller.

  2. Link the scene controller to luminaires – Follow the instructions in Linking.

Configuring Circadian Rhythm

Before you start configuring the WR access point please make sure that the version of this device is at least 79.022

To configure collator you need to enter Collator tab [1] and then click on the gear icon [2]. Next step is to select one of the to types of Circadian Rythm [3]

1.png

Don't worry about the information regarding the synchronisation of the collator with timed events. There is a bug that causes the status of this parameter to display incorrectly

  • 24h Circadian Rythm

3000 kelvin overnight
Fading from 3000 to 4000 between 8.00am and midday
Increasing to 4500 kelvin between 1.00pm and 2.00pm
Fading back to 3000 kelvin between 4.00pm and 6.00pm

  • 12h Circadian Rythm

As above, but the same cycle is also repeated between 8.00pm and 6.00am for night shift workers.

While commissioning you can test if Circadian works by selecting Timed event as 1 (DT8 Demo). It will execute whole circadian cycle in 10 minutes.

After performing all these actions please contact LMS support (lms.support@glamox.com) with request for enabling this feature. In email please include the serial ID of the virtual scene controller.

Time zone in a collator

By default, the WR access point is set to the UK time zone. If you are in a different time zone you will need to contact lms support to set the correct zone otherwise circadian rythm and the scheduler will operate according to the wrong time zone