3.1.30-3.1.38 to 4.1.1 update with Scenarios

3.1.30-3.1.38 to 4.1.1 update with Scenarios

If you have commissioned a site on software 3.1.30-3.1.38 using scenarios and now you want to update to software version 4.1.1 your scenarios will not work.

  • If you are updating from version 3.1.30-3.1.36

Because creation of Scenario template was not implemented in software version 3.1.30-3.1.36 after updating the Vertex to 4.1.1 using port 8080 go to the Control Devices tab.

Previously made Scenarios will be visible with the option to move them. If you want to use previously made Scenarios click this option. Now the Scenario is assigned to this tab and you can use it. Since the templates where not a part of previous software versions create new templates. For more information on how to do that go to 7. Control devices | Creating scenario templates

  • If you are updating from version 3.1.38

When updating from version 3.1.38 with scenarios and scenario templates created in the beta tab of Control Devices you will need to take some additional actions for the scenarios to continue working.

When you update Vertex to 4.1.1 (using port 8080) and restart it, go to the Control Devices tab. Here, for the Scenarios to work again you need to edit each one and change their name. It can be something as simple as adding a space at the end.