LMS E2D VERTEX APC G4 (V4)
How to use it in the LMS design?
See the principles of E2D design and good practices.
How to commission it?
See the Commissioning section.
LMS E2D VERTEX APC G4
PN240909000
DALI-2 certified application controller
Control of luminaires compliant with the DALI-2 standard
Support for DALI-2 compliant input devices
Support for 386 DALI-2 addresses - 3 ports, 64 luminaire addresses per port, and 64 (15 recommended) control device addresses per port
Ability to create extensive operational logic
System scalability via Ethernet network
Built-in web application for commissioning and programming
Electronic over-voltage protection on DALI buses up to 280 V AC and 300 V DC
Detachable terminal plugs (quick connectors)
Power supply and Ethernet daisy chaining
Wifi card embedded
Compatibility with LMS E2D VERTEX APC G3
LED Status
LED | Status | Activity |
|---|---|---|
Power | ON | Powered on |
OFF | No power supply | |
Status | ON | Ready to operate |
Blinking | Startup sequence in progress | |
OFF | Firmware update in progress | |
Network | Green | LAN connection established |
Blinking green | LAN setup mode | |
Blue | Cloud connection established | |
Blinking blue | Cloud setup mode | |
Red | No network connection or disabled | |
DALI | ON | DALI bus short circuit |
Blinking | Data transmission in progress |