Please be aware that this is a legacy version of the support site. If you have software version 3.1.30 or higher go to MODERN Home

(Classic) Control Scenarios

Examples of typical control scenarios, with description, components listed and flow to the Node-RED.

Single office

Open plan office

Classroom

Corridor

Toilet


Single office

Application

single office, kitchen

Application

single office, kitchen

Components

control panel (eg. 2 buttons) + sensor

Savings

  • reducing energy consumption by using daylight

  • automatic switching off after leaving the room

Scenario

The lighting turns on when you press the “ON” button. Luminaries adjust the light intensity depending on the amount of daylight (daylight harvesting). If you have Tunable White (CCT) luminaries, they work according to an HCL schedule. When you leave the room, sensor stops detecting the presence and turns the lighting off after 15 min.

Alternatively, you can turn off the lighting manually using the “OFF” button.

Flow to the Node-RED


Open plan office

Application

open plan office, open space

Application

open plan office, open space

Savings

  • reducing energy consumption by using daylight

  • automatic dimming in your zone after leaving the room

  • automatic switching off after a long absence

Components

control panel (eg. 2 buttons) + sensor

Scenario

The lighting turns on when you press the “ON” button. Luminaires adjust the light intensity depending on the amount of daylight (daylight harvesting). If you have Tunable White (CCT) luminaires, they work according to an HCL schedule. When you leave the room, sensor stops detecting the presence in your zone and dims the lighting after 15 min. If you don’t come back in an hour, the lighting turns off.

Alternatively, you can turn off the lighting manually using the “OFF” button.

Flow to the Node-RED


Classroom

Application

classroom, meeting room, conference room, board room

Application

classroom, meeting room, conference room, board room

Savings

  • reducing energy consumption by using daylight

  • automatic switching off after leaving the room

Components

control panel (eg. 6 buttons) + sensor

Scenario

The lighting turns on automatically. Luminaires adjust the light intensity depending on the amount of daylight (daylight harvesting). If you have Tunable White (CCT) luminaires, they work according to an HCL schedule. When you leave the room, sensor stops detecting the presence and turns the lighting off after 5 min.

You can also adjust the light manually using a control panel.

Flow to the Node-RED


Corridor

Application

corridor

Application

corridor

Savings

  • automatic dimming after leaving the corridor

  • automatic switching off after a long absence

Components

sensor

Scenario

The lighting turns on automatically. When the sensor stops detecting the presence, the lighting dims after 5 min. If nobody comes in 10 min, the lighting turns off.

Flow to the Node-RED


Toilet

Application

toilet, WC, sanitary room

Application

toilet, WC, sanitary room

Savings

  • automatic switching off after leaving the room

Components

sensor

Scenario

The lighting turns on automatically. When you leave the room, sensor stops detecting the presence and turns the lighting off after 5 min.

Flow to the Node-RED