This is only available as a beta release under our early-access program. Reach out your Glamox sales representant if this is interesting
In Glamox Connect can communicate with your local system through our local API. Set up an API, provide connection to your system and you are set to receive all data from the lighting installation as well as the possibility to send commands to the installation.
Setting up local API
The local API is based on MQTT. MQTT use a broker to communicate on topics. In order to set up Glamox Connect local API you need to set up your broker, and pass the configuration to Glamox Connect.
After you have set up your broker, go to Settings → Site → Local API to enter the connection details.
This will connect your access point to the provided broker and it will start to publish and listen to defined topics.
API types
Glamox Connect offers two different API types, Full and Confined. Each API created can be setup with their individual API type
Full
All devices on site will be included in the API automatically. No need to select any devices
Confined
Only allow selected devices to communicate on the API. When setting up the API you will be asked to select devices to be included in the API.
Only selected devices will send updates on the API and commands to the API will only be accepted for devices in the list.
Topics
There are basically three different topic categories:
The <API id> is the name of the API created in Connect. You will find this in the list of created APIs.
Usually this is short for the name, ex. Tenant X will have API ID = tenantx
Discovery topic (config)
Topic where Connect can be asked to describe devices that are available. When a request is being made on <API id>/search
Connect will respond publishing all devices on topic <API id>/<type>/<gateway-id>/<device-id>/config
State topics
As part of payload for discovered device (from discovery topic) is the state_topic for the device. When listening to this topic you will receive all updates for this device. The payload on this topic is only the delta, meaning that values that are NOT in the payload have unchanged value.
Let’s say you have a light where the state update is brightness: 100
and the next update is then color_temp: 400
, the brightness is still 100.
Command topics
For devices who listen to commands you will also get a command_topic on which Connect will listen to commands sent to the device. This topic is part of the device’s config payload on the discovery topic. Changing an attributes value and sending it is as payload to this topic will relay a message to the device.
Device discovery and device types
There are different device types in Glamox Connect and each one of them has their own discovery topic. These are
light
sensor
binary_sensor
When a message has been sent to <API id>/search
, Connect will return the devices on <API id>/<type>/<gateway-id>/<device-id>/config
, for example <API id>/sensor/00201232ab45/100234abc35/config
.
Devices and entities
So we have mentioned device types. Technically this is what we call entities. A device can have one or more entities. That means that one device in Glamox Connect can send more than one entity on the discovery topics.
As an example, most of the devices in our Glamox Wireless Zigbee system will send you a light (luminaire), a sensor (lux sensor) as well as a binary_sensor (occupancy sensor). To signal that this is the same device all entities will have their parent device in the config payload.
Discovery payload
The payload returned on a discovery topic is a config message, describing the entity of the device. ALL entities will give your system essential information on
unique ID’s
which device it is part of
the device_location with location information like floorplan, room and coordinates set in Connect (if present)
which state_topic it will use to send its state updates. The client will need to listen to this topic to get updates for the entity
which command_topic it will use to send its state updates, if the entity can be controlled. The client will need to send command messages to this topic to be able to change values for the entity
Friendly name
In addition the entities have some fields that are specific for the entity
Light
The max value for brightness is given as brightness_scale. I.e. 100 means that the scale is 0-100
If the light has a color_mode this is given as ‘true’ as well as listing the level of control in supported_color_modes
brightness - only brightness control according to brightness_scale
color_temp - color_temp in mired and color_temp_kelvin as kelvin in addition to brightness
color - color control in addition to brightness and color_temp
If you can activate effects on the light, this is given as effect: ‘true’
The effect_list will (if effect) contain a list of effects the light can perform, i.e. ‘identify’ to blink the light
Light config payload (Example has “connect” as API ID):
state_topic: connect/light/001fee00000053a6/17880107102b0c/state schema: json unique_id: 17880107102b0c_light object_id: 17880107102b0c_light device_location: floorplan_name: Floor 3 floorplan_id: 2bbd26bc-c1cc-4c73-b6f0-84cb43b5f8c5 floorplan_point: - '0.7114518843852604' - '0.05005221590401024' room_id: b7d115c2-b910-40b8-93b7-99d6dc8b4535 room_name: LMS device: identifiers: - 17880107102b0c name: 17880107102b0c manufacturer: Glamox Connect API model: Wireless Zigbee suggested_area: mysitename via_device: 001fee00000053a6 command_topic: connect/light/001fee00000053a6/17880107102b0c/set name: Light_17880107102b0c brightness_scale: 100 color_mode: 'true' brightness: 'true' supported_color_modes: - brightness effect: 'true' effect_list: - identify platform: mqtt
Sensor and binary sensor
The device_class will tell you which kind of sensor the entity is
illuminance
temperature
For sensors, the unit_of_measurement is provided to indicate how to interpret the state.
This is NOT available for binary sensors as they are always ‘ON’/'OFF'
A value_template is also included for the integrating system to know what the value field of this sensor is given as. In the example below the state will be reported as
"lux": 480
in the json payload.
Sensor config payload (Example has “connect” as API ID):
state_topic: connect/sensor/001fee00000053a6/17880107102b0c/state schema: json unique_id: 17880107102b0c_illuminance object_id: 17880107102b0c_illuminance device: identifiers: - 17880107102b0c name: 17880107102b0c manufacturer: Glamox Connect API model: Wireless Zigbee suggested_area: glamoxmoldetest via_device: 001fee00000053a6 name: Sensor/Illuminance_17880107102b0c device_class: illuminance unit_of_measurement: lx value_template: '{{ value_json.lux }}' platform: mqtt
Binary_sensor config payload (Example has “connect” as API ID):
state_topic: connect/binary_sensor/001fee00000053a6/17880107102b0c/state schema: json unique_id: 17880107102b0c_occupancy object_id: 17880107102b0c_occupancy device: identifiers: - 17880107102b0c name: 17880107102b0c manufacturer: Glamox Connect API model: Wireless Zigbee suggested_area: glamoxmoldetest via_device: 001fee00000053a6 name: Sensor/Occupancy_17880107102b0c value_template: '{{ value_json.presence }}' device_class: occupancy platform: mqtt
Listening for device updates
As mentioned earlier, each entity will provide their state_topic in the config payload. This means that in order to get the updates for the devices/entities you want, you need to listen to the topics provided.
When an update to a device occur, Glamox Connect will then send the delta on the given state topic. This means that you will NOT get the full state of the entity, only the change. Please note that even though it is the delta, it is possible to get multiple values in the same update
Example:
Given a state for a light as following
{ "brightness": 100, "color_temp": 200, "color_temp_kelvin": 5000, "state": "ON" }
If we change the brightness of the light in the example to 80%, the state update sent on the state_topic will be as following
{ "brightness": 80 }
If a light has been turned on by changing the brightness from previous setting, the message will look something like this
{ "brightness": 80, "state": "ON" }
Similar for sensors, typical status updates will look like this
{ "lux": 670 }
{ "temperature": 25.1 }
{ "presence": "ON" }
Sending commands
If you want to send commands to a device, you will need to send it to the entity on the command_topic provided in the config payload.
Lets look at the previously given config payload for a light. In the config payload we have the following line
command_topic: connect/light/001fee00000053a6/17880107102b0c/set
In this example API ID = connect. This will be different for all APIs and full topic is provided in config payload
To change a value for this entity we need to send a valid json payload to the given topic
Turning the light off:
{ "state": OFF }
Changing brightness:
{ "brightness": 80 }
Device health
We provide device health status for devices through the use of virtual binary sensors entities. These sensors act like any other binary sensors, but whose values are based on certain health states a device can hold.
Health state can be obtained through the state topic for the virtual sensors like for any other entity. Device classes used for these virtual sensors are off either "problem" or "connectivity" class and is used to give meaning to the “ON” / “OFF” values.
Virtual sensors entities for all devices
These virtual sensors are common for all devices:
Virtual sensor | Device class | Description |
---|---|---|
connectivity | connectivity | Indicates whether device is responding as expected. “ON” means that the device is responding. |
maintenance_fault | problem | Indicates if there is a maintenance issue with device. “ON” means that there is a problem. |
Virtual sensor entities only for emergency devices
For emergency devices, we offer the following additional virtual sensors in addition to the common virtual sensors:
Virtual sensor | Device class | Description |
---|---|---|
function_test_failure | problem | Indicates whether last function test failed or not “ON” means that function test has failed. |
duration_test_failure | problem | Indicates whether last duration test failed or not “ON” means that the duration test has failed. |