Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 12 Next »

Power down the controler and remove the wires conected to the DALI buses. Now you can restore power and begin backup restoring.

Do not connect DALI buses into Vertex unit until backup uploading procedure is finished!

  1. Go to Settings section in E2D UI.

2. Login using your admin password if needed.

3. In the Backup section choose and upload the backup file by pressing “Select backup file” button and after choosing the proper file select “Send backup and restore data”.

4. Wait for the backup to upload - it may take several minutes. After the backup uploads, Vertex will be automatically restarted when it has read the new configuration.

  1. Reconnect the wires to the buses.

  2. Use netconfig and choose the previous IP address.

  3. Check if Vertex has restored DALI devices and groups properly.

  • No labels

0 Comments

You are not logged in. Any changes you make will be marked as anonymous. You may want to Log In if you already have an account.