The parameter ON level Presence is automatically the set point for DLR.

If no calibration is performed, the light output adjusts to 500 lux at 100% of ON level presence.
As a example if the parameter is set to 50%, the light output from the luminaire adjusts to 250 lux.

The function is working when “Daylight based control” is enabled.

When manually overriding the DLR functionality will be disabled. The DLR functionality will be enabled again when the hold time expires or a ON level presence command is sent.

When enabling an HCL cycle generated from a Gateway the ON level presence will change according to the light level cycle from the Gateway and this will then change the setpoint accordingly.

DLR works as a stand-alone functionality, meaning it does NOT follow groups or zones.

Be aware that the DLR is based on the readings from the sensor photocell. These readings are based on reflected light from a coverage area. The reflected light from the sensors coverage area might be different from what the user experience in the room.

For a precise measure please calibrate daylight sensor.