Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 12 Next »

Basically, to connect your installation to Glamox Connect you need an Access point as well as gateway(s) connected to your local installation.

The access point is the one point connected to Glamox Connect. The access point communicates to the gateway(s) on the local network.

What do you need?

  1. RevPI + internet connection

  2. Gateways

    1. LMS E2D VERTEX ApC 3 for E2D

    2. Ubisys gateway for Wireless Zigbee

  3. 24V power supply(s) - LMS E2D POWER SUPPLY 24V 30W -

  4. Ethernet switch ports for all access points and gateways - LMS E2D IND SWITCH

Example with multiple DALI gateways connected to Glamox Connect

The Access point needs to be connected to 24V power as well as ethernet connection. There is no hard limit to number of gateways to 1 access point, but recommendations are as follows

DALI Complete: Max 8 gateways per access point

Wireless Zigbee: Max 10 gateways pr access point

Ethernet2DALI: TBC - One cluster is verified ok

The DALI complete gateway has two port for DALI connection, so you will need 1 gateway per two DALI lines in your installation. The DALI gateway is physically connected to the DALI lines, as well as connected to your local IP network. The DALI gateway needs 24V mains connection.

The Wireless Zigbee gateway requires PoE or 230V power supply adapter, as well an ethernet connection.

Detailed information on the Ethernet2DALI gateway can be found here: https://glamox.atlassian.net/wiki/spaces/E2D

The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways.

  • No labels