Info |
---|
Commissioning app version 94+ is required to enable PIR repeating. |
PIR Repeater Disclaimer
Repeating PIR messages on projects SHOULD be the very last resort to on-site troubleshooting and should be used sparingly.
...
Failure to keep PIR repeaters to a minimum can result in an excessive amount of communication traffic between devices, subsequently leading to an unstable/unusable system.
...
Step by step instructions
The Example Scenario:
To the right is a warehouse environment with racking aisles. Each racking aisle has 4 luminaires with presence links between each node.
...
Click ‘Configure’.
Select the last device which received the PIR message. (In this case it would be the 3rd luminaire [1] in each racking aisle).
Tick the ‘Repeater’ box [2].
Info |
---|
Note: The device will turn RED, and you will need to re-write the configuration to the device(s). |
...
4. Click ‘Profiles’ [3].
5. Click the 'PIR' component box [4].
6. Make sure the profile is in advanced mode and long click on ‘Advanced’ [5].
7. You will now see a new ‘HopCount’ option in the left dialog box [6].
8. Set the HopCount value accordingly depending on the situation.
...