Basically, to connect your installation to Glamox Connect you need an Access point as well as a gateway(s) connected to your local installation.

The access point is the one point connected to Glamox Connect. The access point communicates to the gateway(s) on the local network.

What do you need?

...

RevPI + internet connection

...

Gateways

  1. LMS E2D VERTEX ApC 3 for E2D

  2. Ubisys gateway for Wireless Zigbee

...

...

Components

  1. Access point - Access point: LMS CONNECT RevPi Core3+ATLAS

  2. Local gateways to your systems:

    1. Ethernet2Dali (E2D) - LMS E2D VERTEX APC 3 (if you already have it in your installation, you don’t need to add another one) with internet connection

    2. Wireless Zigbee - LMS Zigbee Gateway

    3. DALI Complete - LMS CONNECT DALI/TCP GATEWAY

  3. Ethernet switch ports for all access points

...

  1. - you can use LMS E2D IND SWITCH

Inc drawio
baseUrlhttps://glamox.atlassian.net/wiki
diagramNameGlamox Connect equipment.drawio
imgPageId228556814
serviceAttFile
aspectbfe91b75-5d2c-26a0-9c1d-138518896778 1
width950
includedDiagram1
aspectHashe7c056cbb52bb2fcc8de44e0ece2fdd06a689235
pageId228556814
diagramDisplayNameGlamox Connect equipment.drawio
height440

Example with multiple DALI gateways connected to Glamox Connect

  1. Internet connection

Note

Glamox Connect monitors luminaires as long as they are powered. If you use the manual power switch, the luminaires will be flagged as missing (Maintenance issue and alert). To avoid this, do NOT mount monitored equipment on a power line with "manual" power switch.

Gateways limits

There is no hard limit to the number of gateways to 1 access point , but recommendations are as followsDALI Complete: Max 8 gateways :

  • Ethernet2Dali - max 25 gateways (one cluster) per access point

  • Wireless Zigbee

...

  • - max 10 gateways

...

  • per access point

Ethernet2DALI: TBC - One cluster is verified ok

The DALI complete gateway has two port for DALI connection, so you will need 1 gateway per two DALI lines in your installation. The DALI gateway is physically connected to the DALI lines, as well as connected to your local IP network. The DALI gateway needs 24V mains connection.

The Wireless Zigbee gateway requires PoE or 230V power supply adapter, as well an ethernet connection.

...

  • DALI Complete - max 8 gateways per access point

Info

The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways.