Note

NOTE: Setting of IP on gateways is not yet possible to do on site, without special software. If your system engineer does not have this software and training, the IP’s need to be set up before the gateways are installed

  1. Connect the gateways to power and ethernet

    • If DALI gateway, also connect DALI line(s)

  2. Connect the access point to 24V power and ethernet

  3. Make sure the access point has access to the network where the gateways are connected

    • Only the access point speaks to the Glamox Connect cloud. The access point communicates with all gateways and administer the two-way communication between the gateways and the cloud

  4. Check the serial number on front of access point (5 digits)

  5. Go to URL http://GlamoxConnectCore<serial>.local, for example http://GlamoxConnectCore30288.local if the serial is 30288

  6. Make sure that the IP addresses of the gateways will be consistent, either by IT binding the mac address to an static IP or by assigning static IP

    • The Access point WebUI from 5. will list all gateways on the network with current settings

  7. If you want to change the IP settings on the DALI Gateways you need to use an external tool, as the gateway does not provide any WebUI

  8. If Glamox Wireless Zigbee the gateway needs to be set up with an access code to connect access point to the gateway

    1. Make sure to be on same local network to reach the gateway

    2. Follow gateway manual to go to admin page, default http://192.168.0.211

    3. You can also find the local url (with link) from the access point WebUI

    4. Go to Security tab and activate “Access code”

    5. Use access code 1337 (default for the gateway integration) or the access code part of the QR code on back of gateway.

    6. Press “Activate” to allow for new connections for 5 minutes. The gateway integration needs to start within these 5 minutes. If successful you will see the access point connected to the gateway.

      • This needs to be coordinated with LMS Team (for now). If all the integrations are setup the access point will try to join after reboot.

      • Contact the LMS team if the synchronization and joining is not succesful

...