Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

This article shows how to connect a Kinetic switch when you have a Dongle connected and luminaire are identified.

...

Info

Requires a Glamox Wireless Radio luminaire with CPW2-SEN sensor with firmware version 6.8.135 or newer, if you have older software go to article Connecting DONGLE (BLE) Updating LMS WIRELESS DONGLE

...

Step by step instructions

...

1.1. Enter the Luminaires tab [1] and choose the open the configure option. Click on the desired luminaire with CPW2-sen [2] to pair with the Kinetic switch (this will act as the Kinetic Master).

1.2. Click ‘Configuration' [3] and tick the ‘Enable EnOcean’ box (EO) [4]. A virtual Kinetic switch device will appear next to the device on the drawing [5]. The Kinetic Switch ID will be the digits of the luminiare and a zero (on the drawing you will see a shortcut).

...

To perform these actions go to the Luminaires tab and to the Link option [6].

2.1. Linking virtual Kinetic Switch device and Kinetic Switch Master luminaire to self

Click on the Kinetic Switch Master luminaire [7] and select ‘Link to Self' [8].

...

2.2. Linking virtual Kinetic switch device to Kinetic Master luminaire

Draw a directional presence link from the virtual Kinetic switch [9] to the Kinetic switch Master luminaire [10] .

...

2.3. Linking to other Wireless Radio devices

Draw directional prescence links from the virtual Kinetic switch device [11] to other surrounding devices which need to be controlled by the Kinetic switch.

...

3.1. Enter the ‘Profiles’ tab [12] and from the drop down menu [13] , choose ‘NEW PROFILE’.

3.2. Make sure the Controller type is set to SceneController [14] and in the Advanced mode [15] the Dim Up/Down option is ticked [16].

Info

Dimming down - Long press on a button

Dimming up - Long press, release and long press again immediately after releasing

3.3. Save the changes [17] and remember the profiles number, you will be needing it later.

...

3.4. In the ‘Luminaires’ tab, select the new Virtual Kinetic Switch device [18]. Go to ‘Configure’ [19] and from the ‘Scene Profile’ dropdown menu [20] select the newly created Kinetic switch scene profile.

...

3.5. Enter the ‘Scenes’ tab [21] and select the ‘Kinetic Switch Master’ serial number in the Scene Controller drop down menu [22].

3.6 Apply the linked profiles from the drop down menu [23] and press 'Sync'.

...

3.8 Go back to the ‘Luminaires’ tab and make sure the Kinetic Switch Master Configuration is sync’d.

...

4.1. Click on the virtual Kinetic Switch Luminaire [24].

4.2. Click the ‘Pair’ button [25] to activate commissioning mode.

...