Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

To place the multisensor in the project, you need to remember the typical Ethernet2DALI limitations. The average DALI bus load is 9 mA. The sensor offers both presence and motion detection.Upgrading the sensor to IP54 requires a special mounting box. The sensor will be perfect for corridors and communication paths because of the elliptical presence/motion detection area. During LMS design remember about specifying the detecting directions of the sensor.

Technical data

...

Installation height

...

2 – 6 m

...

Minimum height

...

>1.7 m

...

Installation type

...

Ceiling installation

...

Avarage DALI current consumption

...

10 mA

...

Size of concealed housing

...

Ø55 mm

...

Ambient temperature

...

-15°C ... 50°C

...

Type of protection

...

IP54 (when fitted)

 Detection range

...

Mounting height (A)

...

Diagonally (t)

...

Head on to (R)

...

2 m

...

56 m² | 16 m x 3.5 m

...

56 m² | 16 m x 3.5 m

...

2.5 m

...

88 m² | 22 m x 4 m

...

72 m² | 18 m x 4 m

...

3 m

...

135 m² | 30 m x 4.5 m

...

90 m² | 20 m x 4.5 m

...

3.5 m

...

150 m² | 30 m x 5 m

...

100 m² | 20 m x 5 m

...

4 m

...

150 m² | 30 m x 5 m

...

100 m² | 20 m x 5 m

...

4.5 m

...

150 m² | 30 m x 5 m

...

100 m² | 20 m x 5 m

...

5 m

...

150 m² | 30 m x 5 m

...

100 m² | 20 m x 5 m

...

5.5 m

...

150 m² | 30 m x 5 m

...

100 m² | 20 m x 5 m

...

6 m

...

150 m² | 30 m x 5 m

...

100 m² | 20 m x 5 m

...

Info

The sensor offers 2 instances for motion/presence detection. It means that using one sensor allows for controlling 2 zones independently.

...