To place the multisensor in the project, you need to remember the typical Ethernet2DALI limitations. The average DALI bus load is 9 mA. The sensor offers both presence and motion detection.Upgrading the sensor to IP54 requires a special mounting box. The sensor will be perfect for corridors and communication paths because of the elliptical presence/motion detection area. During LMS design remember about specifying the detecting directions of the sensor.
Technical data
...
Installation height
...
2 – 6 m
...
Minimum height
...
>1.7 m
...
Installation type
...
Ceiling installation
...
Avarage DALI current consumption
...
10 mA
...
Size of concealed housing
...
Ø55 mm
...
Ambient temperature
...
-15°C ... 50°C
...
Type of protection
...
IP54 (when fitted)
Detection range
...
Mounting height (A)
...
Diagonally (t)
...
Head on to (R)
...
2 m
...
56 m² | 16 m x 3.5 m
...
56 m² | 16 m x 3.5 m
...
2.5 m
...
88 m² | 22 m x 4 m
...
72 m² | 18 m x 4 m
...
3 m
...
135 m² | 30 m x 4.5 m
...
90 m² | 20 m x 4.5 m
...
3.5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
4 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
4.5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
5.5 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
6 m
...
150 m² | 30 m x 5 m
...
100 m² | 20 m x 5 m
...
Info |
---|
The sensor offers 2 instances for motion/presence detection. It means that using one sensor allows for controlling 2 zones independently. |
...