  • Areas to be controlled

  • Luminaire presence settings by area i.e.:

    • Is the maximum on level of the luminaires to be reduced?

    • What should the luminaires dim to?

    • What is the standby level?

    • Should the luminaires turn off?

  • Are luminaires to be linked into presence groups?

    • If so, what size of group? Does this differ by area? If so, this must be stated.

  • Can a drawing be provided to the engineer to show which fittings should be grouped?

  • Are there daylight sensors, either remote or integral?

    • If so, which fittings need to be linked to the daylight sensor?

  • Do the fittings need to turn off on daylight or dim to a set level?

  • Are there scene set switches? If so:

    • Which luminaires need to link to the switches?

    • What are the required scenes?

...

  • Control - luminaires to be set to 80% of their maximum and dim to 10% after 2 minutes of no activity. Luminaires will then turn off after a further 5 minutes of no activity.

  • Linking – luminaires to be linked to the fitting on either side to effectively allow groups of 3 fittings to be brought on if presence is detected on any group.

  • Daylight – there is no daylight contribution in this area and therefore no daylight sensors are installed.

  • Scenes – there are no scene sets set switches in this car park

  • Emergency fittings – there are emergency fittings to be identified which are labeled on the drawing and should be manually checked on commissioning and identified as such.

...

  • Control - luminaires to be set to 80% of their maximum and dim to 10% after 2 minutes of no activity. Luminaires will then remain on at 10%.

  • Linking – luminaires to be linked to 4 fittings on either side to allow half the driving aisle to be brought on if presence is detected on any group.

  • Daylight – there is no daylight contribution in this area and therefore no daylight sensors are installed.

  • Scenes – there are no scene sets set switches in this car park

  • Emergency fittings – there are emergency fittings to be identified which are labeled on the drawing and should be manually checked on commissioning and identified as such.

...

  • Daylight – there is unobstructed daylight contribution in this area and 2 daylight sensors are installed.

  • Control – luminaires will be held off by the daylight sensors throughout the daytime period. They will then come on at 60% of their maximum and dim to 25% after 2 minutes of no activity. Luminaires will remain at 25% and never turn off throughout the nighttime period.

  • Linking –

    • the nearest 3 luminaires on the deck to be linked to the last fittings on lift lobby landings The top deck fittings will be linked in 2 groups, one for each half of the car park.

    • The stairwell fitting will, in turn, be linked to the lift lobby landing above.

    • The last luminaire before exiting the ramp on the lower floor will be linked to the first two fittings in the car park to ensure users are always entering a lit area.

  • Scenes – there are no scene sets set switches in this car park

...