This release is mainly focused on solving issue with electrical incompatibility between VERTEX device and some emergency modules, which causes imposibility do discovery all devices connected to DALI buses.

Highlights

News:

  • Temporary disabled functionality of measurement Current and Voltage on DALI BUS

  • Added immediate restart of device while LAN95XX controller freezes

  • Added E2D Analytics features in UI

    • Exceeding number of allowed DALI-2 Input Devices exceeded on DALI bus

    • Address overload - Connected more than 64 devices on bus

    • SNR to high - to big frame errors share in DALI transmission

    • Listing non-normative DALI frame timings devices

Fixes:

  • Solved problem with electrical incompatibility between Vertex3 and some Emergency Modules

  • Fixed problem with detecting

  • Added possibility to connect feedback to Modular in Tablet visualisation

...