The access point is the one point connected to Glamox Connect. The access point communicates to the gateway(s) on the local network.

What do you need?

  1. Access point - RevPI

  2. Internet Connection - you can use LMS E2D REMOTE ACCESS KIT as a GSM gateway,

  3. Local application controllers

    Local gateways:

    1. Ethernet2DALI - LMS E2D VERTEX ApC 3 for E2D

    2. Ubisys gateway for Wireless Zigbee - LMS CONNECT ZIGBEE GATEWAY PoE

    3. DALI Complete - LMS DALI USB GATEWAY

  4. 24V power supply(s) - LMS E2D POWER SUPPLY 24V 30W -

  5. Ethernet switch ports for all access points and gateways - LMS E2D IND SWITCH

  6. Internet connection - you can use LMS E2D REMOTE ACCESS KIT as a GSM gateway

Inc drawio
baseUrlhttps://glamox.atlassian.net/wiki
diagramNameGlamox Connect equipment.drawio
imgPageId228556814
serviceAttFile
aspectbfe91b75-5d2c-26a0-9c1d-138518896778 1
width950
includedDiagram1
aspectHashe7c056cbb52bb2fcc8de44e0ece2fdd06a689235
pageId228556814
diagramDisplayNameGlamox Connect equipment.drawio
height440

...

The Access point needs to be connected to 24V 24 V power as well as ethernet connection. There is no hard limit to the number of gateways to 1 access point, but recommendations are as followsDALI Complete

  • Ethernet2DALI: TBC - One cluster is verified ok

  • Wireless Zigbee: Max

...

  • 10 gateways per access point

...

  • DALI Complete: Max

...

  • 8 gateways

...

  • per access point

Ethernet2DALI

Detailed information on the Ethernet2DALI : TBC - One cluster is verified okgateway can be found here: https://glamox.atlassian.net/wiki/spaces/E2D

Wireless Zigbee

The Wireless Zigbee gateway requires PoE or 230V power supply adapter, as well an ethernet connection.

DALI complete

The DALI complete gateway has two port ports for DALI connection, so you will need 1 gateway per two DALI lines in your installation. The DALI gateway is physically connected to the DALI lines, as well as connected to your local IP network. The DALI gateway needs 24V 24 V mains connection.

The Wireless Zigbee gateway requires PoE or 230V power supply adapter, as well an ethernet connection.

Detailed information on the Ethernet2DALI gateway can be found here: https://glamox.atlassian.net/wiki/spaces/E2D

Info

The gateways do not require any physical connection to the access point. The Access point communicates over TCP/IP to all connected gateways.