Glamox believe believes that every commercial and industrial luminaire should be automatically controlled , and that the control system should be so simple that it can be used by anyone.
This simplicity means that complicated Controls Specifications are not required and that no advance advanced knowledge of the controls or the wiring is required by the specifier, installer or end user.https://drive.google.com/file/d/1iPl35aMX5mIIK2PL4W-s-rjiCspk-cy2/view?usp=sharing
...
Controls Philosophy
The Controls Philosophy for the site can be agreed, or modified, at any time during the installation process. In fact, we can change settings in luminaires during the commissioning process and throughout the installation lifespan with no modifications to the wiring.
...
Control - luminaires to be set to 80% of their maximum and dim to 10% after 2 minutes of no activity. Luminaires will then turn off after a further 5 minutes of no activity.
Linking – luminaires to be linked to the fitting on either side to effectively allow groups of 3 fittings to be brought on if presence is detected on any group.
Daylight – there is no daylight contribution in this area and therefore no daylight sensors are installed.
Scenes – there are no scene sets switches in this car park
Emergency fittings – there are emergency fittings to be identified which are labelled labeled on the drawing and should be manually checked on commissioning and identified as such.
...
Control - luminaires to be set to 100% of their maximum and dim to 50% after 5 minutes of no activity. Luminaires will then remain on at 50%.
Linking – luminaires to be linked to all 20 fittings in the egress area to allow all fittings to be brought on if presence is detected on any group.
Daylight – there is no daylight contribution in this area and therefore no daylight sensors are installed.
Scenes – there are no scene sets switches in this car park
Emergency fittings – there are emergency fittings to be identified which are labelled labeled on the drawing and should be manually checked on commissioning and identified as such.
...
Control - luminaires to be set to 80% of their maximum and dim to 10% after 2 minutes of no activity. Luminaires will then remain on at 10%.
Linking – luminaires to be linked to 4 fittings on either side to allow half the driving aisle to be brought on if presence is detected on any group.
Daylight – there is no daylight contribution in this area and therefore no daylight sensors are installed.
Scenes – there are no scene sets switches in this car park
Emergency fittings – there are emergency fittings to be identified which are labelled labeled on the drawing and should be manually checked on commissioning and identified as such.
...
Control - luminaires to be set to 100% of their maximum and dim to 50% after 5 minutes of no activity. Luminaires will then remain on at 50%.
Linking – luminaires to be linked to all 20 fittings in the egress area to allow all fittings to be brought on if presence is detected on any group.
Daylight – there is no daylight contribution in this area and therefore no daylight sensors are installed.
Scenes – there are no scene sets switches in this car park
Emergency fittings – there are emergency fittings to be identified which are labelled labeled on the drawing and should be manually checked on commissioning and identified as such.
...