For the commissioning process to be as accurate as possible, drawings need to be imported onto the tablet. The most common way to do this is to provide Wireless Radio with drawings when the LiteIP–Tablet–Pack is ordered.A tablet request form is then issued to ensure the address and postcode of the site is captured. At this stage we will also request the gmail account which the OEM/client wish to use going forward. If no gmail account exists we will create one which is generally, lighting.sitexxxx@gmail.com.
Drawings can be manually imported onsite as follows:
...
Select the required settings for this profile:
OnLevel - the maximum on level of the luminaire
FadeTime - the length of time the fitting will take to fade to Standby Level
StandbyLevel - the level of the luminaire once it is dimmed
StandbyTime - the length of time the luminaire remains at the Standby Level
Set at 127.5 for Never Off
PowerOn - enter the wattage of the luminaire at full output
DayNightEnabled - See Application Note - Building Occupied & Unoccupied Mode
Save Changes
...
Device type
Select which device you have in the luminaire
...
G2 Controller - select this if you have a DT10 or DT18 installed
Slimline Controller - select this if you have a Slimline Controller DT19 installed
PIR Timeout
Click PIR > PIRTIMEOUT to enter the desired timeout.
Microwave - select this if you have a Wireless Radio combined M1, M2 or D4i MicrowaveCMW Sensor
The controller box will automatically change to Microwave
Scene Controller - select this if you are setting up a scene controller - DT14, DT23, DT21
No other settings will be applied and you can Save Changes
E3Monitor E3Module - this device can only monitor emergency fittings and not control the luminaire - see Emergency Monitor DT15
Tridonic E3M - This is a specific Tridonic device
select this if you have Wireless Radio stand-alone emergency luminaire
Save Changes
E3Module
If there are emergency fittings of this luminaire type this select the E3 Module Box and the appropriate Emergency Manufacturer. It is not necessary to have a standalone profile for emergency and non-emergency luminaires of the same type.
...
The LDR box can be used to set up Daylight Sensors, Lamp Monitors or Temperature Sensors.
...
Daylight Sensors - if you have a Circular Recessed, Surface IP65 or Conduit Entry Sensor, review the Spec Guide to determine whether to use Sensor Up or Sensor Down
Lamp Monitor - select this if you have a V Sense Monitor
Temperature - select this if you have a Temperature Monitor
Info |
---|
Daylight Sensor , Lamp and Temperature Monitors cannot all be combined in the same G2Controllerluminaire controller. Only one option is available in a Slimline Controller. |
...