Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

For the commissioning process to be as accurate as possible, drawings need to be imported onto the tablet. The most common way to do this is to provide Wireless Radio with drawings when the LiteIP–Tablet–Pack is ordered.A tablet request form is then issued to ensure the address and postcode of the site is captured. At this stage we will also request the gmail account which the OEM/client wish to use going forward. If no gmail account exists we will create one which is generally, lighting.sitexxxx@gmail.com.

Drawings can be manually imported onsite as follows:

...

  • Select the required settings for this profile:

    • OnLevel - the maximum on level of the luminaire

    • FadeTime - the length of time the fitting will take to fade to Standby Level

    • StandbyLevel - the level of the luminaire once it is dimmed

    • StandbyTime - the length of time the luminaire remains at the Standby Level

      • Set at 127.5 for Never Off

    • PowerOn - enter the wattage of the luminaire at full output

    • DayNightEnabled - See Application Note - Building Occupied & Unoccupied Mode

    • Save Changes

...

Device type

  • Select which device you have in the luminaire

...

  • G2 Controller - select this if you have a DT10 or DT18 installed

  • Slimline Controller - select this if you have a Slimline Controller DT19 installed

    • If you have an integral P1, P2 or P4 Occupancy Sensor installed tick PIRENABLED in the PIR Box

    • If you have an integral 230v PIR or Microwave installed, leave PIRENABLED unticked and select Switch in the Controller Box

  • PIR Timeout

    • Click PIR > PIRTIMEOUT to enter the desired timeout.

  • Microwave - select this if you have a Wireless Radio combined M1, M2 or D4i MicrowaveCMW Sensor

    • The controller box will automatically change to Microwave

  • Scene Controller - select this if you are setting up a scene controller - DT14, DT23, DT21

    • No other settings will be applied and you can Save Changes

  • E3Monitor E3Module - this device can only monitor emergency fittings and not control the luminaire - see Emergency Monitor DT15

  • Tridonic E3M - This is a specific Tridonic device

  • select this if you have Wireless Radio stand-alone emergency luminaire

  • Save Changes

E3Module

  • If there are emergency fittings of this luminaire type this select the E3 Module Box and the appropriate Emergency Manufacturer. It is not necessary to have a standalone profile for emergency and non-emergency luminaires of the same type.

...

The LDR box can be used to set up Daylight Sensors, Lamp Monitors or Temperature Sensors.

...

Info

Daylight Sensor , Lamp and Temperature Monitors cannot all be combined in the same G2Controllerluminaire controller.

Only one option is available in a Slimline Controller.

...